Section Contents Page 1 Dimensional information 1 2 Description and operation 2 3 Fixing and wiring 3 4 Programming 6 5 Detection patter
10 User menu functions with dimming applications Using the Programming Handset (Part No. DD-LCDHS) 4. Press and hold the left arrow key. On the main
11 LIGHTS DO NOT COME ON Check to see if the Vitesse Plus marshalling box is powered up and the wiring is correct. Disconnect both RJ45 connectio
12 Ref #WD157 Issue 5 LOAD See datasheet for VitessePlus marshalling box SUPPLY VOLTAGE 12VDC TIME OUT PERIOD Adjustable 10 seconds to 99 minu
2 The VITP-PD/IR presence detector switches are designed to provide automatic control of lighting loads via the VitessePlus marshalling box. They d
3 1. Connect a Cat 5 (RJ45) patch lead from the back of the sensor to the relevant port on the VitessePlus marshalling box. An additional RJ45 conn
4 3. Fixing & Wiring (continued) 2 x VitessePlus RJ45 Connections for Cat 5 patch leads When mounting the detector:- Avoid direct sunlight e
5 Surface Mount Backing Box (Part No. DBB) (not supplied with detector) 3 4 3 4 5 6
6 USING AS A DIMMER When the lighting is switched, the light level can be manually adjusted on a temporary basis. Set the level using the LUX UP
7 4. Programming (continued) Using the Programming Handset (Part No. DD-LCDHS) All the following functions can be programmed using the remote contro
8 4. Programming (continued) 2. Press and hold the left arrow key. On the main menu (―Detector Param‖ will be showing), scroll right until the ―Ch1(
9 3. Press and hold the left arrow key. On the main menu (―Detector Param‖ will be showing), scroll right until the ―Ch2(dim) Set‖ menu appears on t