LOAD
Normally closed contact
2 Amp maximum
Minimum load 100mA
Normally open contact
6 Amp fluorescent lighting and resistive
3 Amp compact fluorescent lighting
3 Amp low energy lighting
3 Amp low voltage lighting (switch primary of transformer)
Fluorescent lighting (max 6 fittings recommended)
For fluorescent lighting total power factor correction ca-
pacitance must not exceed 40μF.
3 Amp fans and ventilation equipment
Switch SON lighting loads via a contactor
Minimum load 100mA
SUPPLY VOLTAGE 220-240 Volts AC 50 Hz
TIME OUT PERIOD Adjustable 10s to 30m
LIGHT LEVEL Light to dark
TERMINAL CAPACITY 2.5 mm
2
MATERIAL Flame retardant ABS
TYPE Class 2
TEMPERATURE -10°C to 35°C
CONFORMITY EMC-89/336/EEC
Part Numbers Specification
Detection Pattern
EBDSPIR-VFC Ceiling mounted
presence detector
voltage free out-
put contact
DBB Surface mounting
back box
Ref #WD234 Issue 3
C.P. Electronics Ltd
Brent Crescent
London
NW10 7XR
United Kingdom
Tel: + 44 (0) 333 900 0671
Fax: + 44 (0) 333 900 0674
www.cpelectronics.co.uk
enquiry@cpelectronics.co.uk
IMPORTANT NOTICE!
This device should be installed by a qualified electrician in
accordance with the latest edition of the IEE wiring regulations.
Due to our policy of continual product improvement CP Electronics reserves the right
to alter the specification of this product without prior notice.
FM 45789 EMS 534520